Semiconductor & IC manufacturing

Wafer fabs, power and compound semiconductors, packaging and test, and MEMS: cleanrooms, ultra-pure water, specialty gas with gas monitoring, abatement and utilities that never stop.

How FacilityOS helps

Platform modules used

Segments

Systems and equipment

Core: every site of this kind has it. Common: most sites have it. Optional: depends on the site.

Chiller plant & PCW

The plant cools MAUs and dry coils; PCW cools tools, pumps and RF generators.

EquipmentLevelPoints worth watchingNotes
Large centrifugal chillerCoreCHW supply temp · CHW return temp · Load · Power draw · Efficiency (kW/ton) · FaultThousand-ton centrifugals (Trane, York, Carrier, Daikin) on BACnet/IP, typically N+1.
Cooling tower cellCoreTower leaving water · Tower entering water · Fan speed · Basin level · Water conductivity · Fan vibration
PumpCoreRunning · Speed · Differential pressureChilled and condenser water pumps; drives usually on Modbus TCP.
Process cooling water loopCoreSupply temp · Return temp · Supply pressure · Supply-return differential · Loop flow · Loop conductivity · Leak detected
Heat-recovery chiller / heat pumpOptionalHot water supply temp · Chilled water supply temp (recovery side) · Power draw · Combined COPHeat recovery displacing boiler gas — one of the main decarbonization levers.
Hot-water boilerCommonHot water supply temp · Firing rate · FaultHot water for MAU preheat and reheat.
Plate heat exchangerCommonSecondary supply temp · Approach · Primary pressure drop
Pressurization / expansion unitCommonSystem pressure · Low pressure alarm · Make-up today
Cooling tower chemical treatmentCommonConductivity · Chemical drum low
Side-stream filterOptionalFilter differential pressure

Cleanroom air

Make-up air, recirculation and FFUs hold cleanliness, the pressure cascade and temperature/humidity.

EquipmentLevelPoints worth watchingNotes
Make-up air unitCoreSupply air temp · Supply dew point · Outdoor airflow · Fan speed · Final filter pressure drop · FaultDew-point control sets cleanroom humidity.
Recirculation air unitCoreSupply air temp · Return air temp · Recirculation airflow · Dry-coil valve · Filter pressure drop
Fan-filter unit bankCoreFFUs running · FFUs in fault · Average speed · Bank power · FFU network faultGroup by feeder or control segment; clustered failures usually mean a circuit.
Cleanroom zoneCorePressure vs adjacent · Room temp · Relative humidity · Downflow velocity · Target class (ISO 14644-1) · Door held openTypical cascade 0.02–0.06 inWC (5–15 Pa).
Particle counterCoreParticles ≥ 0.1 µm · Particles ≥ 0.3 µm · Particles ≥ 0.5 µm · Particles ≥ 5.0 µm · Measured class (ISO equivalent) · Above target ISO classISO 14644-1 limits are per m³; divide by 35.3147 for per ft³.
Cleanroom FMCS summaryCommonWorst zone particles ≥ 0.5 µm · FFUs in fault (all banks) · Zones out of spec
HumidifierCommonControlled humidity · Cylinder / nozzle service
Pass-through / airlock interlockCommonBoth doors open · UV lamp hours
Airborne molecular contamination monitorCommonAcids · Bases (NH₃)
Fab micro-vibration monitorOptionalVC criterion met · Above tool spec

Process utilities: CDA, vacuum, bulk & specialty gas

The tools' lifeblood: lose supply and they stop; a leak is a life-safety matter.

EquipmentLevelPoints worth watchingNotes
Clean dry air compressorCoreDischarge pressure · Output · Load · Power draw · Surge detected · Fault
Desiccant air dryerCorePressure dew point · Pressure drop · Regeneration temp · FaultTypical pressure dew point −94°F (−70°C).
CDA headerCoreHeader pressure · Header dew point · Demand
Bulk gas supplyCoreTank level · Supply pressure · Vaporizer outlet temp · Flow · Impurity · Reserve supply in useN2, O2, Ar, H2, CO2; tank telemetry is usually the gas supplier's.
On-site nitrogen generatorOptionalProduct O2 content · Output · Outlet pressure · Off-purity (on LIN backup)
Specialty gas cabinetCoreCylinder pressure · Delivery pressure · Cylinder weight (scale) · Cabinet exhaust · Excess-flow trip · Auto-shutoff valve closed · Low cabinet exhaustToxic, flammable and corrosive gases live in exhausted cabinets (IFC HPM provisions).
Valve manifold boxCoreDistribution pressure · Sticks open · Enclosure exhaust · Enclosure gas detected · Auto-shutoff valve closed
Specialty gas usage meterCommonCurrent use · Used today (scf) · Days of supply left
Process vacuum pumpCoreInlet pressure · Motor power · N2 purge flow · Pump body temp · Service warningEbara, Edwards and Kashiyama dry pumps, typically Modbus or Profinet.
House vacuum systemCommonVacuum · Pumps running
Bulk chemical delivery systemCoreSupply tank level · Supply pressure · Supply flow · Drip-pan leak · Double-containment leak · Auto-shutoff valve closedAcids, bases and solvents in double-contained piping.
CMP slurry supplyFront-end wafer fab (logic / memory) · Power & compound semiconductor (SiC / GaN) · Packaging & test (OSAT / advanced packaging)CoreDay tank level · Loop supply pressure · Loop flow · Large particles ≥ 1 µm (per mL) · Drip-pan leak
Chemical dilution unitCommonOutlet concentration · Leak · Concentration alarm
Nitrogen purifierCommonOutlet O₂
Tank farm levelCommonLevel · High-high level · Bund leak
Cryogenic vaporizerCommonOutlet gas temp · Low outlet temp

UPW, reclaim & wastewater

UPW quality hits yield directly; wastewater must meet the discharge permit.

EquipmentLevelPoints worth watchingNotes
Reverse osmosis unitCorePermeate conductivity · Permeate flow · Recovery · Membrane differential
Electrodeionization unitCoreProduct resistivity · Product flow
UV TOC reducerCoreUV intensity · Outlet TOC
UPW polishing loopCoreSupply resistivity · TOC · Dissolved oxygen · Dissolved silica · Particles ≥ 0.05 µm (per mL) · Supply flow · Supply pressureTypical targets: 18.2 MΩ·cm and TOC < 1 ppb (tighter at leading-edge nodes).
Water reclaim systemCommonReclaim flow · Reclaim rate · Reclaim conductivity · Reclaim TOC · Diverted to drain (off-spec)
pH neutralization systemCoreEffluent pH · Influent pH · Caustic dosing · Acid dosing · Flow
Fluoride wastewater treatmentFront-end wafer fab (logic / memory) · Power & compound semiconductor (SiC / GaN) · MEMS / sensorsCoreEffluent fluoride · Reactor pH · Clarifier turbidity
CMP slurry wastewaterFront-end wafer fab (logic / memory) · Packaging & test (OSAT / advanced packaging)CommonEffluent turbidity · pH · UF transmembrane pressure
Final effluent monitorCoreDischarge flow · Discharge pH · COD · Fluoride · Discharge temp
Lift stationCommonWet-well level · Pumps running · High level
Domestic water boosterCommonDischarge pressure · Flow
Water tank / reservoir levelCommonLevel · Low level · Overflow level
Resistivity analyzerCommonResistivity

Exhaust & abatement

Tool exhaust must never fail; abatement keeps the air permit.

EquipmentLevelPoints worth watchingNotes
Process exhaust systemCoreExhaust main static · Exhaust airflow · Fans running · Low exhaust staticWatch general, heat, solvent and acid exhaust separately; N+1 fans.
Acid exhaust scrubberCoreRecirculation pH · Recirculation flow · Packing pressure drop · Inlet duct static · Low recirculation flow
Alkaline exhaust scrubberCommonRecirculation pH · Recirculation flow · Packing pressure drop
VOC concentratorCoreInlet VOC · Outlet VOC · Removal efficiency · Desorption temp
Regenerative thermal oxidizerCommonCombustion chamber temp · Inlet solvent (LEL) · Bypass damper open
Point-of-use abatementFront-end wafer fab (logic / memory) · Power & compound semiconductor (SiC / GaN) · MEMS / sensorsCoreCombustion / reaction temp · Inlet pressure · Bypassed (untreated) · Service warningPoint-of-use treatment for PFCs, silane, arsine and the like.

Power & sub-metering

One voltage sag can drop a whole bay of tools.

EquipmentLevelPoints worth watchingNotes
Medium-voltage switchgearCoreBus voltage · Incoming current · Real power · Breaker closed · Protective trip · Relay troubleMonitor only — never operate breakers.
Low-voltage switchgearCoreBus voltage · Load current · Real power · Power factor · Current THD · Breaker trip
Power transformerCoreTop-oil temp · Winding temp · Load · Gas / sudden-pressure alarm · Over-temperature alarm
UPSCoreLoad · Battery runtime · On bypassSNMP v3 (UPS-MIB).
UPS battery string monitorCoreString voltage · Lowest jar voltage · Highest jar voltage · Highest jar internal resistance · Highest jar temp · State of chargePer-jar resistance trending (one of the maintenance practices in IEEE 1188).
GeneratorCommonRunning · Output power · Fuel tank level · Starting battery voltage · Not in AUTO
Power quality meterCommonVoltage THD · Current THD · Voltage sags today · Sag / interruption eventVoltage sags are a common hidden cause of trips.
Site utility meterCoreSite power · Site power (MW) · Energy today · Power factor
Area energy meterCoreArea power · Energy today · 15-min demand · Power factorSub-metering by workshop or system for energy analysis and cost allocation.
Natural gas meterCommonNatural gas flow · Heat input (1,037 BTU/scf) · Gas today (scf)Natural gas in scfh, converted to BTU/h by heating value.
Static transfer switchCoreOn alternate source · Sources out of sync
Battery cell monitoringCommonHighest cell resistance · Cell alarm
-48 V DC power plantCommonDC bus voltage · AC input lost
Insulation monitoring device (IT system)CommonInsulation resistance · Insulation alarm
Busway / cable temperature (DTS)OptionalHottest point
Active harmonic filter (APF)CommonAfter current THD · Unit load · Modules in fault · Fan fault
Passive (tuned) harmonic filterCommonAfter current THD · Capacitor current, measured / rated · Resonance alarm
Automatic capacitor bankCommonPower factor · Capacitor current, measured / rated · Resonance alarm · Switching operations today
Dynamic voltage restorer (DVR)OptionalSags corrected today · On bypass
Power conditionerCommonOutput voltage · Transformer temp
EMI filterOptionalLeakage current
Transformer DGA monitorCommonHydrogen · Acetylene
Bushing monitorOptionalPower factor (tan δ) · Capacitance change
Winding temperature monitorCommonWinding hot spot
On-load tap changer control (OLTC)OptionalTap position · Tap fault · Operations today
Partial discharge monitorCommonDischarge magnitude
Switchgear wireless temperatureCommonHottest point · Phase difference
Arc-flash protection relayCommonArc trip · Protection not ready
Neutral grounding resistor monitorOptionalNGR resistance · Resistor open · Ground fault
Surge arrester monitorOptionalTotal leakage · Resistive current
Flywheel / rotary UPSOptionalFlywheel speed · Discharging · Bearing temp
Tool PDU / EMOCommonEMO pressed

Life safety: gas monitoring, fire, leaks Monitor only

Two-stage alarms set from TLVs; everything monitor-only.

EquipmentLevelPoints worth watchingNotes
Gas monitoring systemCoreActive alarms · Active faults · Auto-shutoff activated · Evacuation alarmThe GMS performs the shut-off interlocks; the platform only monitors.
Silane detectorCoreSilane (SiH4) · Alarm 1 (low) · Alarm 2 (high)TLV 5 ppm.
Ammonia detectorCoreAmmonia level · Ammonia alarmTLV 25 ppm.
Chlorine detectorCoreChlorine (Cl2) · Alarm 1 (low) · Alarm 2 (high)TLV 0.5 ppm.
HF detectorCoreHydrogen fluoride (HF) · Alarm 1 (low) · Alarm 2 (high)TLV-C 2 ppm.
Arsine detectorFront-end wafer fab (logic / memory) · Power & compound semiconductor (SiC / GaN)CommonArsine (AsH3) · Alarm 1 (low) · Alarm 2 (high)TLV 5 ppb; implant and III-V epitaxy.
Phosphine detectorFront-end wafer fab (logic / memory) · Power & compound semiconductor (SiC / GaN)CommonPhosphine (PH3) · Alarm 1 (low) · Alarm 2 (high)TLV 50 ppb.
NF3 detectorCommonNitrogen trifluoride (NF3) · Alarm 1 (low) · Alarm 2 (high)Chamber-clean gas; TLV 10 ppm.
Hydrogen detectorFront-end wafer fab (logic / memory) · Power & compound semiconductor (SiC / GaN)CoreHydrogen (% LEL) · Alarm 1 (low) · Alarm 2 (high)
Oxygen deficiency monitorCoreOxygen · Alarm 1 (O2 below 19.5 %) · Alarm 2 (O2 below 18 %)Nitrogen and inert-gas areas: 19.5 % and 18 % stages.
Fire alarm zone & linkageCoreFire alarm · Supervisory · Trouble · Linkage: air handlers stopped · Linkage: fire/smoke dampers closed · Linkage: smoke exhaust running · Linkage: elevators recalledLinkage proofs verify the fire system did what it should.
Fire alarm panelCoreFire alarm · Supervisory signal · Trouble signalMonitor only (NFPA 72).
Aspirating smoke detectorCommonSmoke obscuration (%/ft) · Alert · Action · Fire 1 · Airflow fault
Leak detection cableCoreLeak detected · Distance to leak · Leak zone · Cable break or contamination
Smoke exhaust fanCommonRunning · Damper not provenSmoke exhaust or stair pressurization fans; monitor only.
Fire / smoke damperCoreClosed · Position fault · Days since test
Clean-agent suppression panelCoreDischarged · Cylinder pressure low

Security & video Monitor only

Camera and door status, and video linkage: cameras are linked to areas, devices and alarm rules; on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm, with a live-view link to the NVR/VMS. Core never contacts a camera.

EquipmentLevelPoints worth watchingNotes
Video cameraCommonOnline · Recording · Motion detected · Video analytics alarm · Tamper (blocked or moved)Status via the VMS (Milestone, Genetec…); on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm — Core never contacts a camera.
Access-controlled doorCommonDoor open · Door held open · Door forcedDoor events can drive camera linkage.
Perimeter intrusion detectionCommonPerimeter alarm
Network switch (SNMP)CommonPorts down · PSU fault

Life-safety equipment (fire alarm, gas detection, emergency power transfer) and protection devices are monitored only. FacilityOS never sends them commands.

Standards and compliance

Standards and complianceNotes
ISO 14644-1Cleanroom classification by airborne particle concentration; fabs typically run ISO 3–5 in front-end and ISO 6–7 in packaging.
ISO 14644-2Monitoring to provide evidence that a cleanroom keeps its class.
SEMI S2EHS guideline for semiconductor manufacturing equipment.
SEMI F63Guide for ultrapure water used in semiconductor processing (typical values on the order of 18.2 MΩ·cm and TOC < 1 ppb).
NFPA 318Standard for the protection of semiconductor fabrication facilities.
International Fire Code (HPM)IFC provisions for hazardous production material (HPM) facilities: gas cabinets, exhaust, gas detection and emergency power.
NFPA 55Compressed Gases and Cryogenic Fluids Code (bulk tanks, cylinder storage).
CGA G-13Storage and handling of silane and silane mixtures.
ACGIH TLVsThreshold limit values for airborne chemicals, commonly used to set gas-detector alarm levels.
NFPA 72National Fire Alarm and Signaling Code.
IEC 62443Security for industrial automation and control systems.
ANSI/ISA-18.2Management of alarm systems for the process industries.

Standards are listed with what they cover; numeric values are typical figures, not requirements for every site. FacilityOS supports your compliance work; it does not certify a site.

KPIs the platform tracks

KPIs the platform tracksNotes
UPW resistivityPolish-loop supply resistivity in MΩ·cm; typical target 18.2.
Worst-zone particlesMaximum ≥ 0.5 µm count across counters, against each zone's ISO class.
CDA dew pointCDA header pressure dew point (°F).
Facility MW & energy per waferUtility service power; kWh per wafer out from MES wafer starts.
Gas alarmsMonthly GMS alarm-1/alarm-2 events and shut-offs.

Reports

ReportsNotes
Daily cleanroom reportPer-zone particle, pressure and T/RH extremes and excursion time for yield analysis.
UPW quality reportResistivity, TOC, DO, particle and silica trends and excursions.
Monthly gas safety reportGMS alarms, shut-offs, detector faults and calibrations due.
Discharge & emissions complianceOutfall pH, fluoride and COD plus scrubber and oxidizer operating records.
Energy by areaEnergy and demand by CUB, sub-fab and cleanroom.

How we deliver

We can take a Semiconductor & IC manufacturing project from survey and design through procurement, installation, commissioning and training — all of it, or only the stages you need.

  1. Site survey & needs assessment
  2. Solution design
  3. Procurement
  4. Installation
  5. Commissioning & acceptance
  6. Training
  7. Go-live & support

Demo site

Hillsboro Wafer Fab

A 24/7 300 mm logic fab: thousand-ton chillers, CDA and bulk gases, ultra-pure water, specialty gas with gas monitoring, ISO 5 cleanrooms and wastewater and exhaust abatement.

Open the Hillsboro Wafer Fab demo site to see this industry with simulated live data: process graphics, video wall, alarm drills and remote adjustment.

Try the live demo

See it with your own equipment

Open the live demo now, or tell us about your site and we will map your equipment and systems to FacilityOS.