Essential electrical system

Life-safety, critical and equipment branches (NFPA 99/110).

EquipmentLevelPoints worth watchingNotes
GeneratorCoreRunning · Output power · Fuel tank level · Starting battery voltage · Not in AUTO
Branch transfer switchCoreOn emergency source · Normal source available · Emergency source available
UPSCoreLoad · Battery runtime · On bypassSNMP v3 (UPS-MIB).
UPS battery string monitorCoreString voltage · Lowest jar voltage · Highest jar voltage · Highest jar internal resistance · Highest jar temp · State of chargePer-jar resistance trending (one of the maintenance practices in IEEE 1188).
Hospital main meterCoreHospital power · Energy today · Power factor
Power quality meterCommonVoltage THD · Current THD · Voltage sags today · Sag / interruption eventVoltage sags are a common hidden cause of trips.
Low-voltage switchgearCoreBus voltage · Load current · Real power · Power factor · Current THD · Breaker trip
Natural gas meterCommonNatural gas flow · Heat input (1,037 BTU/scf) · Gas today (scf)Natural gas in scfh, converted to BTU/h by heating value.
Battery cell monitoringCommonHighest cell resistance · Cell alarm
Insulation monitoring device (IT system)CommonInsulation resistance · Insulation alarm
Isolated power panel (LIM)CoreTotal hazard current · LIM alarm
Generator paralleling switchgearCommonSets online · Not in AUTO
Diesel fuel systemCoreBulk tank level · Runtime at full load · Leak alarm
Load bankOptionalApplied load · Exhaust temp
Voltage stabilizer / AVROptionalOutput voltage · On bypass
Isolation / K-rated transformerCommonWinding temp
Residual current monitor (RCM)CommonLargest residual current · Residual current alarm

Central plant

24/7, N+1.

EquipmentLevelPoints worth watchingNotes
ChillerCoreCHW supply temp · CHW return temp · Load · Power draw · Efficiency · FaultMid-size plant chillers on BACnet/IP.
Cooling towerCoreFan speed · Condenser water supply temp
PumpCoreRunning · Speed · Differential pressure
Hot-water boilerCoreHot water supply temp · Hot water return temp · Firing rate · Flue gas temp · Fault
Steam boilerCommonSteam pressure · Firing rate · Drum water level · Low-water cutoff · FaultSterile processing and humidification.
MRI chillerHospitalCoreMagnet helium level · Cooling water supply temp · Cold head stopped
Absorption chillerOptionalCHW supply temp · Crystallization alarm
Pressurization / expansion unitCommonSystem pressure · Low pressure alarm · Make-up today
Chilled-water storage tankOptionalState of charge
Ice storageOptionalIce inventory
District heating substationOptionalSecondary supply temp
Hot-water boiler burner controlCommonFiring rate · Burner lockout
Steam trap monitoringOptionalTraps failed · Estimated steam loss

ORs, isolation rooms & medical gas

Pressure and medical gas are directly tied to patient safety.

EquipmentLevelPoints worth watchingNotes
Surgery air handlerHospital · Ambulatory surgery centerCoreSupply air temp · Supply air humidity · Supply fan speed · Final (HEPA) filter pressure drop
Operating roomHospital · Ambulatory surgery centerCorePressure vs corridor (positive) · OR temp · OR humidity · Air changes per hourASHRAE 170: positive pressure, 20–60 %RH.
Isolation room (AIIR)HospitalCorePressure vs corridor (negative) · Air changes per hour · Door openAIIR negative pressure (CDC guidance commonly ≥ 0.01 inWC).
Bulk oxygen tankHospitalCoreBulk tank level · Oxygen line pressure · Reserve in use
Medical air plantHospital · Ambulatory surgery centerCoreMedical air line pressure · Dew point · Carbon monoxide
Medical vacuum plantHospital · Ambulatory surgery centerCoreMedical vacuum · Load
Medical refrigeratorCoreCabinet temp · Door open · Power failure
Medical freezerCoreCabinet temp · Power failure
Ultra-low freezer (−80°C)Clinical & research labsOptionalCabinet temp · Power failure
Fume hoodClinical & research labsCoreFace velocity · Low airflow
Biosafety cabinetClinical & research labsCoreInflow velocity · Downflow velocity · Airflow alarm
Power conditionerCommonOutput voltage · Transformer temp
EMI filterOptionalLeakage current
Medical gas alarm panel / zone valve boxCorePressure alarm · Oxygen pressure
Pneumatic tube systemCommonTransactions today · Jams · Blower fault
Washer-disinfectorCommonA0 value · Cycle failed
Blood bank refrigeratorCoreCabinet temp
Mortuary refrigeratorCommonCabinet temp
Hyperbaric chamberOptionalChamber pressure · Chamber oxygen · Fire suppression fault
Operating room control panelCommonRoom temp · Pressure · Medical gas alarm

Patient-area HVAC

Comfort and infection control.

EquipmentLevelPoints worth watchingNotes
VAV air handlerCoreSupply air temp · Supply fan speed · Filter pressure drop
Exhaust fanCoreRunning · Speed
VRF outdoor unitCommonPower · Error code
VRF indoor unitCommonRoom temp
HumidifierCommonControlled humidity · Cylinder / nozzle service
Chilled beam / radiant panelOptionalRoom temp · Condensation alarm
Snow-melt systemOptionalSlab temp
Presence / occupancy sensorCommonOccupied · Battery

Domestic hot water

Legionella control and scald prevention.

EquipmentLevelPoints worth watchingNotes
Domestic hot waterCoreStorage temp · Mixed outlet temp · Recirculation return temp
Domestic water boosterCommonDischarge pressure
Water tank / reservoir levelCommonLevel · Low level · Overflow level
Domestic hot water recirculationCommonReturn temp
Legionella risk monitoringCommonRisk score
Water softenerCommonOutlet hardness · Salt low
Sewage ejector / grease interceptorCommonLevel · High level · Grease layer
Trash compactorCommonFullness · Full

Life safety & clinical systems Monitor only

Defend in place; the platform only notifies.

EquipmentLevelPoints worth watchingNotes
Fire alarm panelCoreFire alarm · Supervisory signal · Trouble signalMonitor only (NFPA 72).
Fire alarm zone & linkageCoreFire alarm · Supervisory · Trouble · Linkage: air handlers stopped · Linkage: fire/smoke dampers closed · Linkage: smoke exhaust running · Linkage: elevators recalledLinkage proofs verify the fire system did what it should.
Fire pumpCommonRunning · System pressure · Power phase failure
Sprinkler riserCommonRiser pressure · Waterflow alarm · Valve tamper
Smoke exhaust fanCommonRunning · Damper not provenSmoke exhaust or stair pressurization fans; monitor only.
Nurse callHospital · Ambulatory surgery centerCoreOpen calls · Code Blue active · System trouble
ElevatorHospitalCommonPassenger entrapment · Door fault
Fire / smoke damperCoreClosed · Position fault · Days since test
Stair pressurization fanCoreStair pressure · Fault · Not in AUTO
Central emergency lighting supply (EPS)CoreBattery fault · Days since 90-min test
Fire door monitoringCommonClosed doors found open
Voice evacuation systemCoreAmplifier fault · Evacuation active

Security & video Monitor only

Camera and door status, and video linkage: cameras are linked to areas, devices and alarm rules; on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm, with a live-view link to the NVR/VMS. Core never contacts a camera.

EquipmentLevelPoints worth watchingNotes
Video cameraCommonOnline · Recording · Motion detected · Video analytics alarm · Tamper (blocked or moved)Status via the VMS (Milestone, Genetec…); on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm — Core never contacts a camera.
Access-controlled doorCoreDoor open · Door held open · Door forcedPharmacy, infant protection and behavioral-health units.
IntercomCommonCalls waiting

Life-safety equipment (fire alarm, gas detection, emergency power transfer) and protection devices are monitored only. FacilityOS never sends them commands.

Standards and compliance

Standards and complianceNotes
NFPA 99Health Care Facilities Code (essential electrical systems, medical gas and vacuum).
NFPA 110Emergency and standby power systems.
NFPA 101Life Safety Code (health care occupancies).
ASHRAE/ASHE 170Ventilation of health care facilities.
CDC Guidelines for Environmental Infection Control (2003)Environmental infection control in health-care facilities, including isolation room pressure.
ASHRAE 188Legionellosis risk management.
USP <797> / <800>Sterile compounding and hazardous drug handling.
The Joint Commission EC/EMEnvironment of Care and Emergency Management standards.
NSF/ANSI 49Biosafety cabinetry.

Standards are listed with what they cover; numeric values are typical figures, not requirements for every site. FacilityOS supports your compliance work; it does not certify a site.

KPIs the platform tracks

KPIs the platform tracksNotes
Isolation pressure complianceShare of time each AIIR stayed negative.
OR pressure & humidity complianceShare of time positive and within 20–60 %RH.
Generator test complianceMonthly load tests done on time and passed.
Pharmacy cold-chain excursionsMonthly excursions.

Reports

ReportsNotes
EES test recordsGenerator and ATS tests (NFPA 110, Joint Commission).
Pressure compliance reportOR and isolation room pressure logs.
Water management recordsHot-water temperatures and Legionella control (ASHRAE 188).
Cold-chain logPharmacy and blood bank temperatures.

How we deliver

We can take a Healthcare project from survey and design through procurement, installation, commissioning and training — all of it, or only the stages you need.

  1. Site survey & needs assessment
  2. Solution design
  3. Procurement
  4. Installation
  5. Commissioning & acceptance
  6. Training
  7. Go-live & support

Demo site

Mesa Valley Medical Center

A 320-bed acute-care hospital: dual-generator emergency power, surgery suite and isolation rooms, medical gases and a pharmacy cold chain.

Open the Mesa Valley Medical Center demo site to see this industry with simulated live data: process graphics, video wall, alarm drills and remote adjustment.

Try the live demo

See it with your own equipment

Open the live demo now, or tell us about your site and we will map your equipment and systems to FacilityOS.