Electronics & flat-panel display

Panel fabs, touch and module assembly, and SMT electronics: huge cleanrooms and FFU fields, chemical supply, wet-bench exhaust, nitrogen reflow and ESD control.

How FacilityOS helps

Platform modules used

Segments

Systems and equipment

Core: every site of this kind has it. Common: most sites have it. Optional: depends on the site.

Chiller plant & PCW

Panel fabs have enormous cooling loads; the plant is the largest power user.

EquipmentLevelPoints worth watchingNotes
Large centrifugal chillerLCD / OLED panel fabCoreCHW supply temp · CHW return temp · Load · Power draw · Efficiency (kW/ton) · FaultThousand-ton centrifugals (Trane, York, Carrier, Daikin) on BACnet/IP, typically N+1.
ChillerTouch & module assembly · SMT / PCBA electronics assemblyCoreCHW supply temp · CHW return temp · Load · Power draw · Efficiency · FaultMid-size plant chillers on BACnet/IP.
Cooling tower cellCoreTower leaving water · Tower entering water · Fan speed · Basin level · Water conductivity · Fan vibration
PumpCoreRunning · Speed · Differential pressureChilled and condenser water pumps; drives usually on Modbus TCP.
Process cooling water loopLCD / OLED panel fabCoreSupply temp · Return temp · Supply pressure · Supply-return differential · Loop flow · Loop conductivity · Leak detected
Heat-recovery chiller / heat pumpOptionalHot water supply temp · Chilled water supply temp (recovery side) · Power draw · Combined COPHeat recovery displacing boiler gas — one of the main decarbonization levers.
Process chillerTouch & module assembly · SMT / PCBA electronics assemblyCommonProcess water supply temp · Process water return temp · Load

Cleanroom & environment

FFU-field availability, pressure and particles drive point-defect rates.

EquipmentLevelPoints worth watchingNotes
Make-up air unitLCD / OLED panel fab · Touch & module assemblyCoreSupply air temp · Supply dew point · Outdoor airflow · Fan speed · Final filter pressure drop · FaultDew-point control sets cleanroom humidity.
Fan-filter unit bankCoreFFUs running · FFUs in fault · Average speed · Bank power · FFU network faultGroup by feeder or control segment; clustered failures usually mean a circuit.
Cleanroom zoneCorePressure vs adjacent · Room temp · Relative humidity · Downflow velocity · Target class (ISO 14644-1) · Door held openTypical cascade 0.02–0.06 inWC (5–15 Pa).
Particle counterCoreParticles ≥ 0.1 µm · Particles ≥ 0.3 µm · Particles ≥ 0.5 µm · Particles ≥ 5.0 µm · Measured class (ISO equivalent) · Above target ISO classISO 14644-1 limits are per m³; divide by 35.3147 for per ft³.
Cleanroom FMCS summaryLCD / OLED panel fabCommonWorst zone particles ≥ 0.5 µm · FFUs in fault (all banks) · Zones out of spec
Air handlerSMT / PCBA electronics assemblyCommonSupply air temp · Duct static pressure
ESD monitoringSMT / PCBA electronics assembly · Touch & module assemblyCoreStations monitored · Stations failing now · Floor humidity · Wrist strap / footwear fail · Bench ground faultHumidity is usually held somewhere in 30–70 %RH (site-specific).
Airborne molecular contamination monitorCommonAcids · Bases (NH₃)
Fab micro-vibration monitorOptionalVC criterion met · Above tool spec

Production equipment status

Reflow and AOI status on SMT lines.

EquipmentLevelPoints worth watchingNotes
Reflow oven (N2)SMT / PCBA electronics assemblyCorePeak zone temp · Tunnel O2 (N2 atmosphere) · N2 flow · Conveyor speed · FaultNitrogen reflow typically holds a few hundred to 1,000 ppm O2.
Automated optical inspectionSMT / PCBA electronics assemblyCoreBoards inspected today · True defect rate · False-call rate
Line controller (OEE)SMT / PCBA electronics assembly · Touch & module assemblyCommonOEE · Output (parts/h) · Good parts today · Energy per part
Thermal oil heaterCommonOutlet oil temp · Low-flow trip

CDA, nitrogen, specialty gas & chemicals

Array uses silane, ammonia and NF3; wet processes use developer, stripper and etchants.

EquipmentLevelPoints worth watchingNotes
Clean dry air compressorLCD / OLED panel fabCoreDischarge pressure · Output · Load · Power draw · Surge detected · Fault
Air compressorTouch & module assembly · SMT / PCBA electronics assemblyCoreDischarge pressure · Load · Power draw · Fault
Desiccant air dryerCorePressure dew point · Pressure drop · Regeneration temp · FaultTypical pressure dew point −94°F (−70°C).
CDA headerCoreHeader pressure · Header dew point · Demand
Bulk gas supplyCoreTank level · Supply pressure · Vaporizer outlet temp · Flow · Impurity · Reserve supply in useN2, O2, Ar, H2, CO2; tank telemetry is usually the gas supplier's.
On-site nitrogen generatorCommonProduct O2 content · Output · Outlet pressure · Off-purity (on LIN backup)
Specialty gas cabinetLCD / OLED panel fabCoreCylinder pressure · Delivery pressure · Cabinet exhaust · Excess-flow trip · Auto-shutoff valve closed
Valve manifold boxLCD / OLED panel fabCommonDistribution pressure · Enclosure gas detected · Auto-shutoff valve closed
Specialty gas usage meterLCD / OLED panel fabCommonCurrent use · Used today (scf) · Days of supply left
Bulk chemical delivery systemLCD / OLED panel fab · Touch & module assemblyCoreSupply tank level · Day tank level · Supply pressure · Supply flow · Drip-pan leak · Double-containment leak · Auto-shutoff valve closedTMAH developer can be fatal through the skin; treat its leaks at top priority.
Process vacuum pumpLCD / OLED panel fabCommonInlet pressure · Motor power · Service warning
Chemical dilution unitCommonOutlet concentration · Leak · Concentration alarm
Nitrogen purifierCommonOutlet O₂

UPW & wastewater

Panel cleaning uses enormous volumes of UPW.

EquipmentLevelPoints worth watchingNotes
Reverse osmosis unitLCD / OLED panel fabCorePermeate conductivity · Permeate flow
Electrodeionization unitLCD / OLED panel fabCoreProduct resistivity · Product flow
UPW polishing loopLCD / OLED panel fabCoreSupply resistivity · TOC · Supply flow · Supply pressure · Storage tank levelPanel fabs commonly run ≥ 17 MΩ·cm.
Water reclaim systemLCD / OLED panel fabCommonReclaim flow · Reclaim rate · Diverted to drain (off-spec)
pH neutralization systemLCD / OLED panel fab · Touch & module assemblyCoreEffluent pH · Caustic dosing · Flow
Final effluent monitorLCD / OLED panel fabCoreDischarge flow · Discharge pH · COD
Domestic water boosterCommonDischarge pressure · Flow
Resistivity analyzerCommonResistivity

Wet-bench exhaust & abatement

Wet-bench exhaust and scrubbers protect people and the permit.

EquipmentLevelPoints worth watchingNotes
Process exhaust systemCoreExhaust main static · Exhaust airflow · Fans running · Low exhaust staticWet-bench exhaust (acid, alkali and solvent kept separate).
Acid exhaust scrubberLCD / OLED panel fab · Touch & module assemblyCoreRecirculation pH · Recirculation flow · Packing pressure drop
Alkaline exhaust scrubberLCD / OLED panel fabCoreRecirculation pH · Recirculation flow
VOC concentratorLCD / OLED panel fabCoreOutlet VOC · Removal efficiency
Point-of-use abatementLCD / OLED panel fabCommonCombustion / reaction temp · Bypassed (untreated)
Exhaust fanSMT / PCBA electronics assemblyCommonRunning · SpeedReflow exhaust.

Power & sub-metering

Meter array, cell, module and CUB separately.

EquipmentLevelPoints worth watchingNotes
Medium-voltage switchgearLCD / OLED panel fabCoreBus voltage · Incoming current · Real power · Breaker closed · Protective trip · Relay troubleMonitor only — never operate breakers.
Low-voltage switchgearCoreBus voltage · Load current · Real power · Power factor · Current THD · Breaker trip
Power transformerLCD / OLED panel fabCoreTop-oil temp · Winding temp · Load · Gas / sudden-pressure alarm · Over-temperature alarm
TransformerTouch & module assembly · SMT / PCBA electronics assemblyCommonWinding temp · Load · Over-temperature alarmDry-type transformers.
UPSCoreLoad · Battery runtime · On bypassSNMP v3 (UPS-MIB).
UPS battery string monitorCoreString voltage · Lowest jar voltage · Highest jar voltage · Highest jar internal resistance · Highest jar temp · State of chargePer-jar resistance trending (one of the maintenance practices in IEEE 1188).
GeneratorCommonRunning · Output power · Fuel tank level · Starting battery voltage · Not in AUTO
Power quality meterCommonVoltage THD · Current THD · Voltage sags today · Sag / interruption eventVoltage sags are a common hidden cause of trips.
Site utility meterCoreSite power · Site power (MW) · Energy today · Power factor
Area energy meterCoreArea power · Energy today · 15-min demand · Power factorSub-metering by workshop or system for energy analysis and cost allocation.
Natural gas meterCommonNatural gas flow · Heat input (1,037 BTU/scf) · Gas today (scf)Natural gas in scfh, converted to BTU/h by heating value.
Active harmonic filter (APF)CommonAfter current THD · Unit load · Modules in fault · Fan fault
Dynamic voltage restorer (DVR)OptionalSags corrected today · On bypass
Partial discharge monitorCommonDischarge magnitude
Tool PDU / EMOCommonEMO pressed

Life safety Monitor only

Gas monitoring, chemical leaks and fire. Monitor only.

EquipmentLevelPoints worth watchingNotes
Gas monitoring systemLCD / OLED panel fabCoreActive alarms · Active faults · Auto-shutoff activated · Evacuation alarmThe GMS performs the shut-off interlocks; the platform only monitors.
Silane detectorLCD / OLED panel fabCoreSilane (SiH4) · Alarm 1 (low) · Alarm 2 (high)
Ammonia detectorLCD / OLED panel fabCoreAmmonia level · Ammonia alarm
NF3 detectorLCD / OLED panel fabCommonNitrogen trifluoride (NF3) · Alarm 1 (low) · Alarm 2 (high)
HF detectorLCD / OLED panel fabCommonHydrogen fluoride (HF) · Alarm 1 (low) · Alarm 2 (high)
Oxygen deficiency monitorCoreOxygen · Alarm 1 (O2 below 19.5 %) · Alarm 2 (O2 below 18 %)Nitrogen and inert-gas areas: 19.5 % and 18 % stages.
Leak detection cableCoreLeak detected · Distance to leak · Leak zone · Cable break or contamination
Fire alarm zone & linkageCoreFire alarm · Supervisory · Trouble · Linkage: air handlers stopped · Linkage: fire/smoke dampers closed · Linkage: smoke exhaust running · Linkage: elevators recalledLinkage proofs verify the fire system did what it should.
Fire alarm panelCoreFire alarm · Supervisory signal · Trouble signalMonitor only (NFPA 72).
Aspirating smoke detectorCommonSmoke obscuration (%/ft) · Alert · Action · Fire 1 · Airflow fault
Smoke exhaust fanCommonRunning · Damper not provenSmoke exhaust or stair pressurization fans; monitor only.

Security & video Monitor only

Camera and door status, and video linkage: cameras are linked to areas, devices and alarm rules; on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm, with a live-view link to the NVR/VMS. Core never contacts a camera.

EquipmentLevelPoints worth watchingNotes
Video cameraCommonOnline · Recording · Motion detected · Video analytics alarm · Tamper (blocked or moved)Status via the VMS (Milestone, Genetec…); on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm — Core never contacts a camera.
Access-controlled doorCommonDoor open · Door held open · Door forcedDoor events can drive camera linkage.

Life-safety equipment (fire alarm, gas detection, emergency power transfer) and protection devices are monitored only. FacilityOS never sends them commands.

Standards and compliance

Standards and complianceNotes
ISO 14644-1Cleanroom classification; array areas commonly ISO 4–5, cell and module ISO 6–7.
SEMI S2Equipment EHS guideline, widely applied to FPD tools.
NFPA 318Fire protection for semiconductor fabrication facilities, commonly applied to FPD fabs.
ANSI/ESD S20.20ESD control program for electronic parts and assemblies.
IPC J-STD-001Requirements for soldered electrical and electronic assemblies.
IPC-A-610Acceptability of electronic assemblies.
IPC/JEDEC J-STD-033Handling of moisture-sensitive devices (tied to floor humidity).
NFPA 72National Fire Alarm and Signaling Code.
IEC 62443Industrial automation and control system security.

Standards are listed with what they cover; numeric values are typical figures, not requirements for every site. FacilityOS supports your compliance work; it does not certify a site.

KPIs the platform tracks

KPIs the platform tracksNotes
Cleanroom ΔP low pointLowest pressure across clean zones.
FFU availabilityFFUs running ÷ installed.
UPW supply flowgpm, against wet-process demand.
Scrubber pHShare of time each scrubber's pH stayed in range.
Energy per board / panelArea energy ÷ MES output.

Reports

ReportsNotes
FFU health reportFailure distribution, clustering by circuit and replacement plan.
Chemical supply & leak reportLevels, tote changes, annulus and drip-pan alarms and shut-offs.
ESD compliance reportStation failures, humidity excursions and corrections.
Emissions & discharge complianceScrubber pH and flow and outfall records.

How we deliver

We can take a Electronics & flat-panel display project from survey and design through procurement, installation, commissioning and training — all of it, or only the stages you need.

  1. Site survey & needs assessment
  2. Solution design
  3. Procurement
  4. Installation
  5. Commissioning & acceptance
  6. Training
  7. Go-live & support

Demo site

Austin Display Fab

A 24/7 Gen 8.5 display fab: huge FFU cleanrooms, high-capacity chillers and PCW, UPW, specialty gas and bulk chemical delivery, scrubbers and VOC abatement.

Open the Austin Display Fab demo site to see this industry with simulated live data: process graphics, video wall, alarm drills and remote adjustment.

Try the live demo

See it with your own equipment

Open the live demo now, or tell us about your site and we will map your equipment and systems to FacilityOS.