Data centers

Hyperscale, colocation, enterprise, edge and AI/HPC with liquid cooling: cooling, power distribution, batteries and PUE.

How FacilityOS helps

Platform modules used

Segments

Systems and equipment

Core: every site of this kind has it. Common: most sites have it. Optional: depends on the site.

Cooling plant

The plant is the largest non-IT load in PUE.

EquipmentLevelPoints worth watchingNotes
ChillerHyperscale · Colocation · Enterprise · AI / HPC with liquid coolingCoreCHW supply temp · CHW return temp · Load · Power draw
Cooling tower cellHyperscale · Colocation · AI / HPC with liquid coolingCoreTower leaving water · Tower entering water · Fan speed · Basin level · Water conductivity · Fan vibration
PumpHyperscale · Colocation · Enterprise · AI / HPC with liquid coolingCoreRunning · Speed · Differential pressure
Heat-recovery chiller / heat pumpOptionalHot water supply temp · Chilled water supply temp (recovery side) · Power draw · Combined COPHeat recovery displacing boiler gas — one of the main decarbonization levers.
Plate heat exchangerCommonSecondary supply temp · Approach · Primary pressure drop
Pressurization / expansion unitCommonSystem pressure · Low pressure alarm · Make-up today
Chilled-water storage tankOptionalState of charge
Dry cooler / adiabatic coolerCommonLeaving fluid temp
Cooling tower chemical treatmentCommonConductivity · Chemical drum low
Side-stream filterOptionalFilter differential pressure
Vibration / condition sensorCommonVelocity RMS

Data hall air

Rack inlet temperature against the ASHRAE TC9.9 recommended envelope (typically 64.4–80.6°F / 18–27°C).

EquipmentLevelPoints worth watchingNotes
CRAHColocation · Enterprise · AI / HPC with liquid coolingCoreSupply air temp · Return air temp · Fan speed
CRAC (DX)Enterprise · EdgeCoreSupply air temp · Return air temp · Return humidity · Compressor capacity · High head pressure
Fan wallHyperscale · AI / HPC with liquid coolingCoreSupply air temp · Airflow · Fans running · Cold-to-hot aisle pressure
Rack PDUCoreRack power · Highest phase current · Rack inlet temp · Rack inlet humidityRack inlet T/RH often comes from rPDU probes.
Split DX / condensing unitCommonSuction pressure · High-pressure trip
HumidifierCommonControlled humidity · Cylinder / nozzle service
In-row coolerCommonSupply air temp · Leak
Aisle containmentCommonDoor open
Rack environment sensorCoreInlet temp (hottest)

Liquid cooling

AI racks throttle or trip within minutes without liquid cooling.

EquipmentLevelPoints worth watchingNotes
Coolant distribution unitAI / HPC with liquid coolingCoreSecondary supply temp · Secondary flow · Leak detected
Rear-door heat exchangerAI / HPC with liquid cooling · Colocation · EnterpriseCommonWater supply temp · Leaving air temp · Water flow · Leak detected
Leak detectionAI / HPC with liquid cooling · Colocation · HyperscaleCoreLeak detected · Leak location (from start) · Sensing cable break
Immersion cooling tankOptionalFluid temp · Fluid level

Power, UPS & batteries

2N or distributed redundancy; batteries are the last line of defense.

EquipmentLevelPoints worth watchingNotes
Medium-voltage switchgearCoreBus voltage · Incoming current · Real power · Breaker closed · Protective trip · Relay troubleMonitor only — never operate breakers.
Low-voltage switchgearCoreBus voltage · Load current · Real power · Power factor · Current THD · Breaker trip
Power transformerCoreTop-oil temp · Winding temp · Load · Gas / sudden-pressure alarm · Over-temperature alarm
UPSCoreLoad · Battery runtime · On bypassSNMP v3 (UPS-MIB); A and B feeds.
UPS battery string monitorCoreString voltage · Lowest jar voltage · Highest jar voltage · Highest jar internal resistance · Highest jar temp · State of chargePer-jar resistance trending (one of the maintenance practices in IEEE 1188).
Battery roomCommonRoom temp · Relative humidity · Hydrogen alarm
GeneratorCoreRunning · Output power · Fuel tank level · Starting battery voltage · Not in AUTO
Transfer switchCoreFed from source B
PDUCoreOutput power
Overhead buswayHyperscale · Colocation · AI / HPC with liquid coolingCommonBusway power · Highest phase current · Hottest joint temp · Joint over-temperature
Power monitoringCoreIT load · Total facility power · PUE (power usage effectiveness)EPMS roll-up, read-only.
Power quality meterCommonVoltage THD · Current THD · Voltage sags today · Sag / interruption eventVoltage sags are a common hidden cause of trips.
Tenant submeterColocationCommonTenant power · Energy todayPer-customer metering.
Static transfer switchCoreOn alternate source · Sources out of sync
Battery cell monitoringCommonHighest cell resistance · Cell alarm
-48 V DC power plantCommonDC bus voltage · AC input lost
Ring main unitCommonSF6 low · Fault passage indicator
Generator paralleling switchgearCommonSets online · Not in AUTO
Diesel fuel systemCoreBulk tank level · Runtime at full load · Leak alarm
Load bankOptionalApplied load · Exhaust temp
Busway / cable temperature (DTS)OptionalHottest point
Fuel cellOptionalOutput · Fault
Active harmonic filter (APF)CommonAfter current THD · Unit load · Modules in fault · Fan fault
Static var generator (SVG / STATCOM)CommonPF after · Unit load · Modules in fault
Isolation / K-rated transformerCommonWinding temp
Transformer DGA monitorCommonHydrogen · Acetylene
Winding temperature monitorCommonWinding hot spot
Partial discharge monitorCommonDischarge magnitude
Switchgear wireless temperatureCommonHottest point · Phase difference
Arc-flash protection relayCommonArc trip · Protection not ready
Residual current monitor (RCM)CommonLargest residual current · Residual current alarm
Surge protective device (SPD) statusCommonSPD failed · Backup breaker open
Flywheel / rotary UPSOptionalFlywheel speed · Discharging · Bearing temp
Server BMC (Redfish / IPMI)OptionalPower draw · PSU redundancy lost

Life safety Monitor only

Very early smoke detection and leak location. Monitor only.

EquipmentLevelPoints worth watchingNotes
Fire alarm panelCoreFire alarm · Supervisory signal · Trouble signalMonitor only (NFPA 72).
Aspirating smoke detectorCoreSmoke obscuration (%/ft) · Alert · Action · Fire 1 · Airflow fault
Sprinkler riserCommonRiser pressure · Waterflow alarm · Valve tamper
Leak detectionEnterprise · EdgeCommonLeak detected · Leak location (from start)
Fire / smoke damperCoreClosed · Position fault · Days since test
Clean-agent suppression panelCoreDischarged · Cylinder pressure low
Pre-action / dry-pipe valveCommonAir pressure · Valve tripped · Low air
Water mist systemOptionalPump unit not ready · Released

Security & video Monitor only

Camera and door status, and video linkage: cameras are linked to areas, devices and alarm rules; on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm, with a live-view link to the NVR/VMS. Core never contacts a camera.

EquipmentLevelPoints worth watchingNotes
Video cameraCommonOnline · Recording · Motion detected · Video analytics alarm · Tamper (blocked or moved)Status via the VMS (Milestone, Genetec…); on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm — Core never contacts a camera.
Access-controlled doorCoreDoor open · Door held open · Door forcedData hall and cage access.
Intrusion alarm panelCommonIntrusion alarm · Tamper
Perimeter intrusion detectionCommonPerimeter alarm
Visitor managementOptionalVisitors on site · Watch-list hit
Network switch (SNMP)CommonPorts down · PSU fault
Smart rack lockOptionalRack open · Forced open

Life-safety equipment (fire alarm, gas detection, emergency power transfer) and protection devices are monitored only. FacilityOS never sends them commands.

Standards and compliance

Standards and complianceNotes
ASHRAE TC9.9 Thermal GuidelinesThermal guidelines for data processing environments; recommended envelope typically 64.4–80.6°F (18–27°C).
ANSI/TIA-942Telecommunications infrastructure standard for data centers, including rated availability levels.
Uptime Institute Tier Standard: TopologyTier I–IV topology classification.
NFPA 75Fire protection of information technology equipment.
NFPA 76Fire protection of telecommunications facilities.
NFPA 70 (NEC) Article 645Electrical provisions for information technology equipment rooms.
ISO/IEC 30134-2Definition and calculation of PUE.
IEEE 1188Recommended practice for maintenance, testing and replacement of VRLA batteries.
NFPA 855Installation requirements for Li-ion UPS / energy storage.
IEC 62443Industrial automation security (OT network zoning).

Standards are listed with what they cover; numeric values are typical figures, not requirements for every site. FacilityOS supports your compliance work; it does not certify a site.

KPIs the platform tracks

KPIs the platform tracksNotes
PUEFacility power ÷ IT power.
Rack inlet temperatureRacks outside the ASHRAE recommended envelope.
Redundancy headroomRunning units minus needed units per redundancy group.
Battery healthJars more than 30 % above baseline resistance.

Reports

ReportsNotes
Monthly PUE & energyPUE, IT load and cooling energy trends.
Customer power reportPer-customer energy and peaks.
Battery maintenance reportResistance and voltage trends and replacement advice (IEEE 1188).
Incident reportAlarm timeline, redundancy state and recovery time.

How we deliver

We can take a Data centers project from survey and design through procurement, installation, commissioning and training — all of it, or only the stages you need.

  1. Site survey & needs assessment
  2. Solution design
  3. Procurement
  4. Installation
  5. Commissioning & acceptance
  6. Training
  7. Go-live & support

Demo site

Dallas DC-1

A 2.5 MW colocation and AI data center: N+1 chillers, liquid-cooling CDUs and 2N UPS.

Open the Dallas DC-1 demo site to see this industry with simulated live data: process graphics, video wall, alarm drills and remote adjustment.

Try the live demo