Solar glass — Glass manufacturing

Rolled forming, coating and tempering.

Solar glass is a segment of Glass manufacturing. Below are the systems and equipment FacilityOS covers for it, filtered from the Glass manufacturing solution.

How FacilityOS helps

Systems and equipment

Core: every site of this kind has it. Common: most sites have it. Optional: depends on the site.

Batch, melting, forming, finishing

A furnace that loses fire or power for a few hours can freeze: backup power and fuel are essential.

EquipmentLevelPoints worth watchingNotes
Batch plantCoreBatch feed rate · Cullet share · Lowest silo level
Glass melting furnaceCoreCrown temp · Bottom temp · Gas flow · Pull (tons/day) · Glass level · Flame failureFlame supervision and gas safety are done by the burner management system; the platform only monitors.
Annealing lehrCoreEntry temp · Exit temp · Roller speed
Cutting lineCoreLine speed · Defect cut-out · Lites cut today
Tempering furnaceCommonHeating section temp · Quench pressure · Blower power
Line controller (OEE)CommonOEE · Output (parts/h) · Energy per part
Weighbridge / scaleOptionalCurrent weight · Load cell fault

Gas, oxygen & protective gas

Oxy-fuel firing uses a lot of oxygen; the tin bath needs nitrogen-hydrogen.

EquipmentLevelPoints worth watchingNotes
Natural gas meterCoreNatural gas flow · Heat input (1,037 BTU/scf) · Gas today (scf)Natural gas in scfh, converted to BTU/h by heating value.
Bulk gas supplyCoreTank level · Supply pressure · Vaporizer outlet temp · Flow · Impurity · Reserve supply in useN2, O2, Ar, H2, CO2; tank telemetry is usually the gas supplier's.
On-site nitrogen generatorOptionalProduct O2 content · Output · Outlet pressure · Off-purity (on LIN backup)
Oxygen deficiency monitorCommonOxygen · Alarm 1 (O2 below 19.5 %) · Alarm 2 (O2 below 18 %)Nitrogen and inert-gas areas: 19.5 % and 18 % stages.
Tank farm levelCommonLevel · High-high level · Bund leak

Cooling water & air

Furnace, electrodes and tin bath need cooling water; forming uses a lot of compressed air.

EquipmentLevelPoints worth watchingNotes
Cooling tower cellCoreTower leaving water · Tower entering water · Fan speed · Basin level · Water conductivity · Fan vibration
PumpCoreRunning · Speed · Differential pressureChilled and condenser water pumps; drives usually on Modbus TCP.
Air compressorCoreDischarge pressure · Load · Power draw · Fault
Compressed-air headerCommonHeader pressure · Air demand · Receiver pressure
Process chillerOptionalProcess water supply temp · Process water return temp · Load

Flue gas treatment

NOx and particulate permits.

EquipmentLevelPoints worth watchingNotes
Process exhaust systemCoreExhaust main static · Exhaust airflow · Fans running · Low exhaust staticWatch general, heat, solvent and acid exhaust separately; N+1 fans.
Dust collectorCoreFilter pressure drop · Spark detectedBatch house and furnace charging dust.

Power, electric boost & emergency power

Electric boost is a big load; the emergency generator keeps furnace cooling and combustion air running.

EquipmentLevelPoints worth watchingNotes
Medium-voltage switchgearCoreBus voltage · Incoming current · Real power · Breaker closed · Protective trip · Relay troubleMonitor only — never operate breakers.
Power transformerCoreTop-oil temp · Winding temp · Load · Gas / sudden-pressure alarm · Over-temperature alarm
Low-voltage switchgearCoreBus voltage · Load current · Real power · Power factor · Current THD · Breaker trip
Motor control centerCommonMCC load · Current · Power factor · Current THD
Area energy meterCoreArea power · Energy today · 15-min demand · Power factorSub-metering by workshop or system for energy analysis and cost allocation.
Site utility meterCoreSite power · Site power (MW) · Energy today · Power factor
Power quality meterCommonVoltage THD · Current THD · Voltage sags today · Sag / interruption eventVoltage sags are a common hidden cause of trips.
GeneratorCoreRunning · Output power · Fuel tank level · Starting battery voltage · Not in AUTO
UPSCoreLoad · Battery runtime · On bypassSNMP v3 (UPS-MIB).
UPS battery string monitorCoreString voltage · Lowest jar voltage · Highest jar voltage · Highest jar internal resistance · Highest jar temp · State of chargePer-jar resistance trending (one of the maintenance practices in IEEE 1188).
Passive (tuned) harmonic filterCommonAfter current THD · Capacitor current, measured / rated · Resonance alarm
Automatic capacitor bankCommonPower factor · Capacitor current, measured / rated · Resonance alarm · Switching operations today
12 / 18-pulse front endOptionalInput current THD · Bridge current unbalance

Life safety Monitor only

Monitor only.

EquipmentLevelPoints worth watchingNotes
Fire alarm panelCoreFire alarm · Supervisory signal · Trouble signalMonitor only (NFPA 72).
Fire pumpCommonRunning · System pressure · Power phase failure
Sprinkler riserCommonRiser pressure · Waterflow alarm · Valve tamper
Combustible gas detectorCommonCombustible gas (LEL) · Gas alarm

Security & video Monitor only

Camera and door status, and video linkage: cameras are linked to areas, devices and alarm rules; on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm, with a live-view link to the NVR/VMS. Core never contacts a camera.

EquipmentLevelPoints worth watchingNotes
Video cameraCommonOnline · Recording · Motion detected · Video analytics alarm · Tamper (blocked or moved)Status via the VMS (Milestone, Genetec…); on an alarm the gateway takes an ONVIF snapshot and attaches it to the alarm — Core never contacts a camera.
Access-controlled doorCommonDoor open · Door held open · Door forcedDoor events can drive camera linkage.

Life-safety equipment (fire alarm, gas detection, emergency power transfer) and protection devices are monitored only. FacilityOS never sends them commands.

Standards and compliance

Standards and complianceNotes
NFPA 86Standard for ovens and furnaces.
NFPA 85Boiler and combustion systems hazards code (burner management).
ASTM C1036Flat glass.
ASTM C1048Heat-strengthened and fully tempered flat glass.
40 CFR 63 Subpart SSSSSSUS EPA area-source emission standards for glass manufacturing.
ISO 50001Energy management systems.

Standards are listed with what they cover; numeric values are typical figures, not requirements for every site. FacilityOS supports your compliance work; it does not certify a site.

Segments of Glass manufacturing

Full Glass manufacturing solution →

How we deliver

We can take a Glass manufacturing project from survey and design through procurement, installation, commissioning and training — all of it, or only the stages you need.

  1. Site survey & needs assessment
  2. Solution design
  3. Procurement
  4. Installation
  5. Commissioning & acceptance
  6. Training
  7. Go-live & support

See it with your own equipment

Open the live demo now, or tell us about your site and we will map your equipment and systems to FacilityOS.